Intermediate

Power Factor Calculator — AC Power Triangle (P, Q, S, cos φ)

Calculate the power factor (cos φ), reactive power Q and apparent power S for an AC circuit. Choose from three input modes: P + Q, P + S, or V × I × PF.

Input mode

kW

Real (active) power actually consumed — e.g. 8 kW

kVAR

Power stored and returned by inductors/capacitors — e.g. 6 kVAR
Power factor
0.8000

cos φ = P / S • φ = 36.87°

True power (P)
8 kW
Reactive power (Q)
6 kVAR
Apparent power (S)
10 kVA
Phase angle (φ)
36.87°
Power factor
0.8
Efficiency
80%
P (kW)Q (kVAR)S (kVA)Power triangle: S² = P² + Q² • PF = P / S = cos φ
Step by step
  1. 1

    Apparent power S = √(P² + Q²)

    √(8² + 6²) = 10
    S is the hypotenuse of the power triangle.
  2. 2

    Power factor = P ÷ S

    8 ÷ 10 = 0.8000
Results are estimates for general information only and are not professional advice — always verify important results independently before relying on them. Read the full disclaimer.
Quick answer

How does this calculator work?

Power factor PF = P / S = cos φ, where P (kW) is true power and S (kVA) = √(P² + Q²) is apparent power, with Q (kVAR) being reactive power. A PF of 1 means purely resistive — all power does useful work. Industrial inductive loads typically have PF 0.7–0.9, leading utilities to require power factor correction.

Formula
S = √(P² + Q²) • PF = cos φ = P / S • Q = S sin φ
How this is calculated

In an AC circuit, the load impedance can be partly reactive (inductive motors, capacitors, transformers). Reactive components store and return energy every cycle rather than consuming it, creating a phase difference φ between the voltage and current waveforms. This gives rise to three distinct power quantities.

True (active) power P [kW] is the power actually converted to work or heat — the rate at which the load consumes energy. Reactive power Q [kVAR] is the power exchanged back and forth with reactive elements each cycle; it does no net useful work but must flow through the wiring and supply. Apparent power S [kVA] = V_rms × I_rms is the total burden on the supply — what the generator and cables must handle. These three form the power triangle: S² = P² + Q². The power factor PF = cos(φ) = P / S is a dimensionless ratio from 0 to 1 showing what fraction of apparent power is actually doing useful work. A PF of 1.0 means a purely resistive load; a PF of 0.8 means 80% of the VA drawn is being used productively.

Low power factor (below ~0.85) is penalised by electricity utilities because it increases line currents and equipment ratings without delivering additional real power. Power factor correction — typically adding shunt capacitor banks to counteract inductive motor loads — raises PF toward 1. The vector diagram shows P along the real (horizontal) axis, Q along the reactive (vertical) axis, and S as their vector sum — identical to the phasor representation of the power triangle.

Frequently asked questions

A power factor of 0.8 means only 80% of the apparent power (kVA) drawn from the supply is converted to useful work (kW). To deliver 800 kW of real power with PF = 0.8, the supply must provide 1000 kVA of apparent power, and the remaining 200 kVAR circulates as reactive power. This wastes cable and transformer capacity.

Inductive loads — electric motors, transformers, fluorescent lighting ballasts, HVAC compressors — draw lagging current (current lags voltage), reducing PF below 1. Capacitive loads cause leading current. Industrial facilities add capacitor banks to counteract inductive loads and keep PF above 0.9 as required by utilities.

kW (kilowatt) = real (true) power doing useful work. kVA (kilovolt-ampere) = apparent power = V_rms × I_rms; it is the capacity the supply must have. kVAR (kilovolt-ampere reactive) = reactive power circulating without doing work. The power triangle links them: kVA² = kW² + kVAR².

Also known as

power factor calculator
ac power triangle
cos phi calculator
kw kva kvar calculator
true power reactive power apparent power
power factor correction calculator
phase angle ac circuit

APA

TG we-Calculate Editorial Team. (2026). Power Factor Calculator — AC Power Triangle (P, Q, S, cos φ) [Online calculator]. TG we-Calculate. https://we-calculate.com/calculator/power-factor-calculator

Chicago

TG we-Calculate Editorial Team. "Power Factor Calculator — AC Power Triangle (P, Q, S, cos φ)." TG we-Calculate. 2026. https://we-calculate.com/calculator/power-factor-calculator.

IEEE

TG we-Calculate Editorial Team, "Power Factor Calculator — AC Power Triangle (P, Q, S, cos φ)," TG we-Calculate, 2026. [Online]. Available: https://we-calculate.com/calculator/power-factor-calculator

BibTeX

@misc{wecalculate_power_factor_calculator, title = {Power Factor Calculator — AC Power Triangle (P, Q, S, cos φ)}, author = {{TG we-Calculate Editorial Team}}, howpublished = {\url{https://we-calculate.com/calculator/power-factor-calculator}}, year = {2026}, note = {TG we-Calculate} }

Did this calculator help you?