Intermediate

Wire Size Calculator — Conductor Cross-Section & Voltage Drop

Enter the load current, wire length, supply voltage and maximum allowable voltage drop — get the next standard IEC cross-section (mm²), its AWG equivalent, the actual drop and the heat lost in the wire.

A

Continuous current the wire must carry

m

Distance from source to load — calculator doubles for the return path

V

Nominal system voltage (e.g. 230 V AC or 12 V DC)

%

IEC 60364 / NEC recommend ≤ 3 % for branch circuits, ≤ 5 % total

Conductor material

Recommended wire size
2.50mm²

Next standard IEC 60228 size above the calculated minimum of 1.6 mm²

US equivalent
AWG 12
Wire resistance (2-way)
0.276 Ω
Actual voltage drop
4.41 V (1.92 %)
Power lost in wire
70.62 W
98%
2%
Load voltage
Wire voltage drop
How the supply voltage splits between the load and the wire
4.41V0.28ΩI = 16AVoltage drop across the wire: V_drop = I × R_wire
Step by step
  1. 1

    Max allowable voltage drop

    230 × 3 ÷ 100 = 6.9
  2. 2

    Minimum wire area A_min = 2·L·I·ρ ÷ V_drop

    2 × 20 × 16 × 0.01724 ÷ 6.9 = 1.5991
    A_min = 2·L·I·ρ / V_drop_max — the smallest area that keeps drop within the limit.
  3. 3

    IEC standard size (rounded up)

    2.50
    Next IEC 60228 cross-section at or above the calculated minimum.
Results are estimates for general information only and are not professional advice — always verify important results independently before relying on them. Read the full disclaimer.
Quick answer

How does this calculator work?

A_min = 2 × L × I × ρ / V_drop_max gives the minimum conductor area in mm², rounded up to the next IEC standard size and its AWG equivalent. Copper ρ = 0.01724 Ω·mm²/m, aluminium ρ = 0.02825 Ω·mm²/m. IEC/NEC recommend ≤ 3 % drop for branch circuits.

Formula
A_min = 2 × L × I × ρ / V_drop_max • V_drop = I × (2Lρ / A)
How this is calculated

Current flowing through a conductor with resistance R produces a voltage drop V = I × R. For a round-trip length of 2L (current goes to the load and returns through the neutral/return wire), the wire resistance is R = 2Lρ/A, where ρ is the conductor resistivity in Ω·mm²/m and A is the cross-sectional area. Rearranging gives the minimum area required to stay within the target drop: A_min = 2LIρ / V_drop_max. Copper at 20 °C has ρ ≈ 0.01724 Ω·mm²/m; aluminium is roughly 64 % more resistive at 0.02825 Ω·mm²/m.

The calculated minimum area is rounded up to the next standard IEC 60228 cross-section (0.75 → 1.0 → 1.5 → 2.5 → 4.0 → 6.0 → … mm²). The actual drop is then computed with that area — it is always at or below the target. The US AWG equivalent is the next gauge whose area meets or exceeds the recommended mm² size. The power dissipated as heat in the wire is P = I²R.

This calculator assumes a single-phase or DC round-trip circuit at ambient temperature with published 20 °C resistivity. In practice resistance rises with temperature, bundled or conduit runs may require current de-rating, and local electrical codes may impose additional safety margins. For safety-critical or high-current installations, always consult a licensed electrician and the applicable national standard (IEC 60364, NEC, BS 7671, or equivalent).

Frequently asked questions

Conductors are manufactured in fixed standard cross-sections (0.75, 1.0, 1.5, 2.5, 4.0 mm² …). The exact calculated minimum rarely coincides with one of those sizes, so the tool always rounds up to guarantee the voltage drop stays within your chosen limit.

IEC 60364 and the US NEC both recommend no more than 3 % drop on a branch circuit and no more than 5 % total (feeder + branch). Use a tighter 1–2 % limit for sensitive electronics or long low-voltage DC runs (12 V, 24 V solar or LED), where a higher percentage represents a large absolute volt loss.

No — the formula uses the factor 2 for a single-phase or DC round trip. For balanced three-phase circuits replace the 2 with √3 ≈ 1.732 in the voltage-drop formula; most three-phase cable-sizing tables already incorporate this factor.

Also known as

wire gauge calculator
cable cross section calculator
conductor size calculator
voltage drop wire calculator
awg wire size calculator
electrical cable sizing
mm2 cable calculator
wire ampacity calculator

APA

TG we-Calculate Editorial Team. (2026). Wire Size Calculator — Conductor Cross-Section & Voltage Drop [Online calculator]. TG we-Calculate. https://we-calculate.com/calculator/wire-size-calculator

Chicago

TG we-Calculate Editorial Team. "Wire Size Calculator — Conductor Cross-Section & Voltage Drop." TG we-Calculate. 2026. https://we-calculate.com/calculator/wire-size-calculator.

IEEE

TG we-Calculate Editorial Team, "Wire Size Calculator — Conductor Cross-Section & Voltage Drop," TG we-Calculate, 2026. [Online]. Available: https://we-calculate.com/calculator/wire-size-calculator

BibTeX

@misc{wecalculate_wire_size_calculator, title = {Wire Size Calculator — Conductor Cross-Section & Voltage Drop}, author = {{TG we-Calculate Editorial Team}}, howpublished = {\url{https://we-calculate.com/calculator/wire-size-calculator}}, year = {2026}, note = {TG we-Calculate} }

Did this calculator help you?