Intermediate

kVA Calculator — Apparent Power, Real Power & Power Factor

Calculate apparent power (kVA), real power (kW) and reactive power (kVAR) for any AC electrical circuit. Enter voltage and current, or switch mode to input real power or apparent power directly, along with the power factor.

Known quantities

V

A

Cosine of the phase angle between voltage and current (0.01–1)
Apparent Power
2.300kVA

kVA = kW ÷ power factor — the total load the supply must deliver

Apparent power (S)
2.3 kVA
Real power (P)
1.955 kW
Reactive power (Q)
1.212 kVAR
Power factor
0.85
Efficiency
85 %
Real (kW)1.955 kW
Reactive (kVAR)1.212 kVAR
230VI = 10AApparent current in circuit at the input voltage
Step by step
  1. 1

    Volt-amperes (VA)

    230 × 10 = 2,300
  2. 2

    Apparent power kVA = VA ÷ 1000

    2,300 ÷ 1000 = 2.300
结果仅为一般参考性的估算,并非专业建议——在依赖这些重要结果之前,请务必自行独立核实。 阅读完整免责声明.
快速解答

这个计算器是如何工作的?

kVA = V × I / 1000 (apparent power). kW = kVA × PF (real power). kVAR = kVA × √(1 − PF²) (reactive power). Power factor PF = kW / kVA ranges 0–1; at PF 1 all kVA equals kW. Low PF means the supply must source more kVA than the load actually uses productively.

公式
kVA = V × I ÷ 1000 • kW = kVA × PF • kVAR = kVA × √(1 − PF²) • PF = cos φ
How this is calculated

In an alternating current (AC) system, three distinct power quantities describe how energy flows. Real power (P, kW) is the power actually converted to useful work — heat, light, motion. Apparent power (S, kVA) is the total power supplied by the generator or transformer, the product of RMS voltage and RMS current. Reactive power (Q, kVAR) is the power that oscillates between the source and inductive/capacitive loads (motors, transformers) without performing net work.

The three form a right triangle — the power triangle — where S² = P² + Q². The power factor (PF = cos φ) is the ratio P/S, ranging from 0 (purely reactive) to 1.0 (purely resistive, perfect efficiency). A low power factor means the supply must deliver more kVA to provide the same kW of useful work, increasing cable sizes, transformer ratings, and energy costs. Utilities often penalise industrial customers with PF below 0.85–0.95.

This calculator works for balanced single-phase or three-phase equivalent circuits. For three-phase systems, multiply the single-phase kVA by 3 (for three single-phase loads) or use √3 × V_line × I_line / 1000 as the apparent power — the per-phase power factor relationship remains the same.

常见问题

kW (kilowatts) is real power — the useful work done. kVA (kilovolt-amperes) is apparent power — the total load the electrical supply must handle. kVA = kW ÷ power factor. When the power factor is 1.0, kVA = kW. For a motor with PF 0.8, a 10 kW load draws 12.5 kVA from the supply.

The power factor is usually on the equipment nameplate or in the technical datasheet. Resistive loads (heaters, incandescent bulbs) have PF ≈ 1.0; induction motors typically run at 0.7–0.9; fluorescent lighting without correction is often 0.5–0.6. A clamp meter that measures both watts and VA can calculate PF directly.

Generators and UPS systems are rated in kVA, not kW, because they must supply apparent power. Size your generator by summing the kVA of all loads (using each load's PF) and adding a 20–25% safety margin. A 10 kW load at PF 0.8 requires at least 12.5 kVA, so a 15 kVA generator is typical for that load.

也称为

kva计算器
视在功率计算器
kva转kw
功率因数计算器
无功功率计算器
kva kw换算
视在功率有功功率无功功率
发电机kva选型

APA

TG we-Calculate Editorial Team. (2026). kVA Calculator — Apparent Power, Real Power & Power Factor [Online calculator]. TG we-Calculate. https://we-calculate.com/zh/calculator/kva-calculator

Chicago

TG we-Calculate Editorial Team. "kVA Calculator — Apparent Power, Real Power & Power Factor." TG we-Calculate. 2026. https://we-calculate.com/zh/calculator/kva-calculator.

IEEE

TG we-Calculate Editorial Team, "kVA Calculator — Apparent Power, Real Power & Power Factor," TG we-Calculate, 2026. [Online]. Available: https://we-calculate.com/zh/calculator/kva-calculator

BibTeX

@misc{wecalculate_kva_calculator, title = {kVA Calculator — Apparent Power, Real Power & Power Factor}, author = {{TG we-Calculate Editorial Team}}, howpublished = {\url{https://we-calculate.com/zh/calculator/kva-calculator}}, year = {2026}, note = {TG we-Calculate} }

这个计算器对您有帮助吗?